• Ultra-lintels are typically installed by a Builder or Bricklayer and it is very important that the following instructions are followed during installation.
  • Lintels must be placed with the rough side facing up in order to provide a proper key into the mortar above.
  • Lintels must be propped at intervals not exceeding 1500mm until the mortar has matured.
  • The minimum bearing onto the brickwork is 100mm (spans up to 1200mm) and 150mm (spans >1200mm). this is based on the assumption of a minimum brick crushing strength of 20 MPa
110×170 Concrete Ultralintel110×80 Concrete Ultralintel
1800900
21001200
24001500
27001800
30002100
33002400
36002700
39003000
42003300
45003600
5000
6000